Ridgelake Condominiums (Pool), located at 900 Ridgelake Dr Peachtree City, GA 30269, received a score of 65 points out of a possible 100 points during their 07/23/2026 inspection by the Georgia Department of Public Health.
The violations noted by the inspector were:
Violation #1:
5 – emergency phone operational and accessible
511-3-5-.18(10)(c ) – (c) an operable, hard-wired, conventional telephone line or continuous powered source, weatherproof emergency phone shall be permanently installed in a conspicuous location within the pool enclosure and must be readily available to bathers at all tim
Points: 15
Corrected during inspection?: No
Repeat: No
Inspector Notes: Observed that the emergency phone does not ring when dialing 911; after dialing 911, the operator called the phone back to ask if there was an emergency. The Fayette County 911 Call Center was able to confirm that when the phone dials 911 that they receive a signal, but nothing is heard on the pool side of the phone. 911 states that had we not answered their return call that emergency services was going to be sent. As 911 is able to receive a signal indicating an emergency and will send emergency services, the pool and spa are left open, however, this shall be immediately addressed. Code: An operable, hard-wired, conventional telephone line or continuous powered source, weatherproof emergency phone shall be permanently installed in a conspicuous location within the pool enclosure and must be readily available to bathers at all times. The emergency phone shall be capable of connecting to 911 and electronically transferring an automatic number identification and automatic locator identification of the pool emergency phone to the public safety answering point, if available. A 911 sign or the names and phone numbers of the nearest available police, fire, ambulance service or rescue unit shall be posted nearby.
Violation #2:
15 – depth and no diving markers, step marking; installed and contrasting
511-3-5-.18(3)(h) – (h) depth markers number and letters shall be tile and four inches minimum in height. numbers shall be of contrasting color to the background on which they are applied.
Points: 4
Corrected during inspection?: No
Repeat: Yes
Inspector Notes: There is no “FT” marking for the depth marker inside the pool. Depth markers number and letters shall be tile and four inches minimum in height. Numbers shall be of contrasting color to the background on which they are applied.
Violation #3:
17 – skimmers/gutters maintained and operable
511-3-5-.11(3)(g) – (g) the skimmer equalizer lines shall be protected by an approved cover/grated with a flow rating equal the maximum system flow divided by the number of skimmers in the system or the maximum flow rating of the skimmer, whichever is greater.
Points: 4
Corrected during inspection?: No
Repeat: Yes
Inspector Notes: There is no cover over the equalizer lines in the pool wall. This must be corrected immediately. The skimmer equalizer lines shall be protected by an approved cover/grated with a flow rating equal the maximum system flow divided by the number of skimmers in the system or the maximum flow rating of the skimmer, whichever is greater.
Violation #4:
17 – skimmers/gutters maintained and operable
511-3-5-.11(3)(d) – (d) each skimmer shall have a weir that adjusts automatically to variations in water level over a minimum range of four inches.
Points: 4
Corrected during inspection?: No
Repeat: No
Inspector Notes: There are no weirs on skimmers. Code: Each skimmer shall have a weir that adjusts automatically to variations in water level over a minimum range of four inches.
Violation #5:
19 – adequate turnover rate
511-3-5-.07(1)(a) – (a) the equipment for a swimming pool shall be of adequate size to turn over the entire pool water capacity. the turnover rate for pools constructed after the adoption of this chapter shall not exceed the sum of one and one-half times the average wat
Points: 5
Corrected during inspection?: No
Repeat: No
Inspector Notes: The flowmeter does not appear to be functioning, and the turnover rate cannot be verified. The weight is all the way at the bottom of the flow meter; however, the pump and filter appear to function properly. The required flow for the pool is 228 gpm. Must be corrected immediately. For any pool that does not meet proper turnover rate two (2) times in a row, it may be deemed that changes need to occur to the filtration system or further investigation as to why turnover cannot be met. Code: The equipment for a swimming pool shall be of adequate size to turn over the entire pool water capacity. The turnover rate for pools constructed after the adoption of this chapter shall not exceed the sum of one and one-half times the average water depth in feet; where the number of hours is equal to the number feet calculated or exceed once every six hours whichever is less. Unless the rate is otherwise specified in subsection (b) below. This system shall be designed to give the proper turnover rate based on the manufacturer’s recommended maximum pressure flow of the filter in dirty media condition of the filter, immediately prior to cleaning the filter.
Violation #6:
22 – signs: peak occupancy/pool/spa/signs legible and in clearview
511-3-5-.18(12)(a) – (a) the words “no diving” and the universal international symbol for “no diving” shall be permanently visible at the edge of the deck for water five feet in depth or less, placed only on the deck beside the depth markers, and shall conform to that ou
Points: 2
Corrected during inspection?: No
Repeat: Yes
Inspector Notes: The No Diving symbol does not meet the 4-inch size requirement; universal symbol for No diving is not present on the deck. Code: The words “No Diving” and the universal international symbol for “NO DIVING” shall be permanently visible at the edge of the deck for water five feet in depth or less, placed only on the deck beside the depth markers, and shall conform to that outlined for depth markers. These must be in compliance prior to permitting 2028.
Violation #7:
36 – daily recordkeeping: water testing and self inspection performed
511-3-5-.22(12) – (12) a safety self-inspection shall be conducted daily by the trained operator or responsible person and documented on a log sheet.
Points: 5
Corrected during inspection?: No
Repeat: No
Inspector Notes: Observed that there is no available information to verify a daily safety check is being performed. Code: A safety self-inspection shall be conducted daily by the trained operator or responsible person and documented on a log sheet.