Southampton Village (Main Pool), located at 200 Carriage Oak Dr Tyrone, GA 30290, received a score of 57 points out of a possible 100 points during their 09/10/2026 inspection by the Georgia Department of Public Health.
The violations noted by the inspector were:
Violation #1:
6 – proper disinfectant level
.17((1)(c) – proper disinfectant level
Points: 15
Corrected during inspection?: No
Repeat: Yes
Inspector Notes: The chlorine level does not meet minimum requirement of at least 2ppm. Must be corrected prior to re-inspection. The pool operates as a stabilized pool. Code: Chlorine in stabilized pools must be between 2pp-10ppm.
Violation #2:
7 – ph between 7.2 and 7.8
511-3-5-.17(2) – (2) chemical values: ph
Points: 15
Corrected during inspection?: No
Repeat: Yes
Inspector Notes: The pH does not meet minimum requirement of 7.2ppm. Code: pH should be maintained between 7.2 and 7.8. Must be corrected prior to permitting.
Violation #3:
12 – grab/hand rails, ladders installed and secure
511-3-5-.06(3)(f)1. – 1. handrails, if removable, shall be installed in such a way that they cannot be removed without the use of tools.
Points: 2
Corrected during inspection?: No
Repeat: No
Inspector Notes: The handrail is not secured to the deck. Ensure handrails are secured back to the decking to prevent them from pulling up during use. Code: Handrails, if removable, shall be installed in such a way that they cannot be removed without the use of tools.
Violation #4:
14 – vacuum line protected
511-3-5-.10(7) – (7) the vacuum line shall be protected with a self-closing, self-latching fitting that complies with the current iampo sps 4- special use suction fitting for swimming pools, spas and hot tubs.
Points: 5
Corrected during inspection?: No
Repeat: No
Inspector Notes: The vacuum line is not covered with the required fitting. . Replace with fitting that is self-closing and self-latching. Code: The vacuum line shall be protected with a self-closing, self-latching fitting that complies with the current IAMPO SPS 4- Special Use Suction Fitting for Swimming Pools, Spas and Hot Tubs.
Violation #5:
17 – skimmers/gutters maintained and operable
511-3-5-.11(3)(d) – (d) each skimmer shall have a weir that adjusts automatically to variations in water level over a minimum range of four inches.
Points: 4
Corrected during inspection?: No
Repeat: No
Inspector Notes: A weir is not present in each skimmer. Replace weirs. Code: Each skimmer shall have a weir that adjusts automatically to variations in water level over a minimum range of four inches.
Violation #6:
19 – adequate turnover rate
511-3-5-.07(1)(a) – (a) the equipment for a swimming pool shall be of adequate size to turn over the entire pool water capacity. the turnover rate for pools constructed after the adoption of this chapter shall not exceed the sum of one and one-half times the average wat
Points: 5
Corrected during inspection?: No
Repeat: Yes
Inspector Notes: The turnover is not adequate for the pool type and size. The required flow for the pool is 222 gpm. The numbers on the flowmeter are worn off. The flowmeter must be replaced so that the flow can be accurately read. Must be corrected immediately. For any pool that does not meet proper turnover rate two (2) times in a row, it may be deemed that changes need to occur to the filtration system or further investigation as to why turnover cannot be met. Code: The equipment for a swimming pool shall be of adequate size to turn over the entire pool water capacity. The turnover rate for pools constructed after the adoption of this chapter shall not exceed the sum of one and one-half times the average water depth in feet; where the number of hours is equal to the number feet calculated or exceed once every six hours whichever is less. Unless the rate is otherwise specified in subsection (b) below. This system shall be designed to give the proper turnover rate based on the manufacturer’s recommended maximum pressure flow of the filter in dirty media condition of the filter, immediately prior to cleaning the filter.
Violation #7:
22 – signs: peak occupancy/pool/spa/signs legible and in clearview
511-3-5-.18(12)(a) – (a) the words “no diving” and the universal international symbol for “no diving” shall be permanently visible at the edge of the deck for water five feet in depth or less, placed only on the deck beside the depth markers, and shall conform to that ou
Points: 2
Corrected during inspection?: No
Repeat: Yes
Inspector Notes: The “No Lifeguard on Duty” sign does not meet the code requirements for the correct letter height of 4 inches. The lifeguard is not always on duty and therefore, the sign must be correct. Code: Where no lifeguard is on duty, a sign or signs shall be placed in clear view at or near the entrance to the pool and shall state in clearly legible letters at least four inches high “WARNING – NO LIFE GUARD ON DUTY and RISK OF DROWNING – SUPERVISE CHILDREN CLOSELY”.
Violation #8:
22 – signs: peak occupancy/pool/spa/signs legible and in clearview
511-3-5-.18(13)(c) – (c) a sign shall be posted stating the hours of operation in clear view near the entrance and shall state the theoretical peak occupancy.
Points: 2
Corrected during inspection?: No
Repeat: Yes
Inspector Notes: The peak occupancy for the pool is not posted. The peak occupancy is 225. Code: A sign shall be posted stating the hours of operation in clear view near the entrance and shall state the theoretical peak occupancy.
Violation #9:
22 – signs: peak occupancy/pool/spa/signs legible and in clearview
511-3-5-.18(12)(a) – (a) the words “no diving” and the universal international symbol for “no diving” shall be permanently visible at the edge of the deck for water five feet in depth or less, placed only on the deck beside the depth markers, and shall conform to that ou
Points: 2
Corrected during inspection?: No
Repeat: Yes
Inspector Notes: The words “No Diving” on the deck do not meet the minimum height requirement of 4-inch lettering for the depth markers. There is no universal symbol for No Diving present at each depth marker. Code: The words “No Diving” and the universal international symbol for “NO DIVING” shall be permanently visible at the edge of the deck for water five feet in depth or less, placed only on the deck beside the depth markers, and shall conform to that outlined for depth markers. Correct prior to permitting 2028.
Violation #10:
35 – operator facility inspections performed; written documentation
511-3-5-.22(6) – (6) written documentation of the operator’s visits must be available at the pool facility. at a minimum, the written record must indicate the condition of the following items:
Points: 4
Corrected during inspection?: No
Repeat: Yes
Inspector Notes: There is limited documentation to verify the CPO is checking the required information as indicated in the code. Records are present, but the records are not in order and scattered and the exact process or documentation of the CPO can not be followed. Code: Written documentation of the operator’s visits must be available at the pool facility. At a minimum, the written record must indicate the condition of the following items: circulation, filtration, and disinfection systems, safety equipment onsite, pool stairs and deck condition, water chemistry results, and corrective actions taken, if needed.
Violation #11:
36 – daily recordkeeping: water testing and self inspection performed
511-3-5-.22(9) – (9) water testing frequency. the trained operator or responsible person shall collect water samples from the water in the pool for monitoring. an in-line sampling port may be used for water held in reservoirs. the water quality testing frequency shal
Points: 5
Corrected during inspection?: No
Repeat: No
Inspector Notes: There is no available documentation onsite to verify a daily safety check is conducted. Code: A safety self-inspection shall be conducted daily by the trained operator or responsible person and documented on a log sheet.
Violation #12:
37 – other violations of the chapter
Points: 1
Corrected during inspection?: No
Repeat: No
Inspector Notes: The facility is exempt from the requirements of a drinking fountain/deck shower. However, a dressing shower is present on site. The dressing shower does not function properly. If equipment is present, then it should function properly and be in good working order.
Violation #13:
37 – other violations of the chapter
Points: 1
Corrected during inspection?: No
Repeat: No
Inspector Notes: The alkalinity does not meet minimum requirements. Adjust the alkalinity in the pool, then verify the pH is within proper range. Code: .17(2) Alkalinity is required to be at 60ppm minimum and 180 ppm maximum.
Additional remarks:
Facility is technically closed. There is a sign on the gate that indicates the pool is closed. However, the gate has been propped open with a rock and if someone came to use the pool, they would not see the sign. Additionally, the sign in log for the pool is present on the outdoor table.
No reinspection will be done since the facility is closed.
Pressure gauges: 18, 20, 0psi
Flowmeters: 85 and 50 gpm.