The Gates in Peachtree City receives a 64% on their recent Pool inspection

Follow The Gates in Peachtree City receives a 64% on their recent Pool inspection

Get notified by email when this case is updated.

The Gates, located at 150 Gates Entry Way Peachtree City, Ga 30269, received a score of 64 points out of a possible 100 points during their 07/21/2026 inspection by the Georgia Department of Public Health.

The violations noted by the inspector were:

Violation #1:
3 – compliant drain covers secure, present and no cracks
511-3-5-.23(5)(f) – (f) broken, unsecured, or missing main drain, or any submerged suction outlet cover/grate
Points: 15
Corrected during inspection?: No
Repeat: Yes
Inspector Notes: The main drain grate at the deeper end of the pool is broken and must be replaced. the previous main drain that was broken has been changed; the other main drain is now broken. See pics. Main drain grates must remain in good repair. Must be corrected prior to reinspection and reopening. Code: Imminent health hazard: Broken, unsecured, or missing main drain, or any submerged suction outlet cover/grate

Violation #2:
3 – compliant drain covers secure, present and no cracks
511-3-5-.23(5)(f) – (f) broken, unsecured, or missing main drain, or any submerged suction outlet cover/grate
Points: 15
Corrected during inspection?: No
Repeat: Yes
Inspector Notes: The main drain grate near the mushroom has one screw present and must be secured on both ends to prevent someone from lifting the grate or other hazards that may occur. Must be corrected prior to reinspection and reopening. Code: Imminent health hazard: Broken, unsecured, or missing main drain, or any submerged suction outlet cover/grate

Violation #3:
15 – depth and no diving markers, step marking; installed and contrasting
511-3-5-.18(3)(h) – (h) depth markers number and letters shall be tile and four inches minimum in height. numbers shall be of contrasting color to the background on which they are applied.
Points: 4
Corrected during inspection?: No
Repeat: Yes
Inspector Notes: The letters on the depth markers do not meet minimum height requirement of 4″. Code: Depth markers number and letters shall be tile and four inches minimum in height. Numbers shall be of contrasting color to the background on which they are applied. Correct prior to permitting season 2028

Violation #4:
17 – skimmers/gutters maintained and operable
511-3-5-.11(3)(d) – (d) each skimmer shall have a weir that adjusts automatically to variations in water level over a minimum range of four inches.
Points: 4
Corrected during inspection?: No
Repeat: Yes
Inspector Notes: A weir is not present in each skimmer. Replace weirs. Code: Each skimmer shall have a weir that adjusts automatically to variations in water level over a minimum range of four inches.

Violation #5:
19 – adequate turnover rate
511-3-5-.07(1)(a) – (a) the equipment for a swimming pool shall be of adequate size to turn over the entire pool water capacity. the turnover rate for pools constructed after the adoption of this chapter shall not exceed the sum of one and one-half times the average wat
Points: 5
Corrected during inspection?: No
Repeat: Yes
Inspector Notes: he flowmeter does not appear to be functioning and the turnover rate cannot be verified. The weight is all the way at the bottom of the flow meter; however, the pump and filter appear to function properly. The required flow for the pool is 228 gpm. Code: The equipment for a swimming pool shall be of adequate size to turn over the entire pool water capacity. The turnover rate for pools constructed after the adoption of this chapter shall not exceed the sum of one and one-half times the average water depth in feet; where the number of hours is equal to the number feet calculated or exceed once every six hours whichever is less. Unless the rate is otherwise specified in subsection (b) below. This system shall be designed to give the proper turnover rate based on the manufacturer’s recommended maximum pressure flow of the filter in dirty media condition of the filter, immediately prior to cleaning the filter. Must be corrected prior to routine inspection.

Violation #6:
22 – signs: peak occupancy/pool/spa/signs legible and in clearview
511-3-5-.18(12)(b) – (b) where no lifeguard is on duty, a sign or signs shall be placed in clear view at or near the entrance to the pool and shall state in clearly legible letters at least four inches high “warning – no life guard on duty and risk of drowning – supervis
Points: 2
Corrected during inspection?: No
Repeat: Yes
Inspector Notes: The “No Lifeguard on Duty” sign does not meet the code requirements for the required height requirement of 4″. The Risk of Drowning portion is too small. Code: Where no lifeguard is on duty, a sign or signs shall be placed in clear view at or near the entrance to the pool and shall state in clearly legible letters at least four inches high “WARNING – NO LIFE GUARD ON DUTY and RISK OF DROWNING – SUPERVISE CHILDREN CLOSELY”.

Violation #7:
22 – signs: peak occupancy/pool/spa/signs legible and in clearview
511-3-5-.18(12)(a) – (a) the words “no diving” and the universal international symbol for “no diving” shall be permanently visible at the edge of the deck for water five feet in depth or less, placed only on the deck beside the depth markers, and shall conform to that ou
Points: 2
Corrected during inspection?: No
Repeat: No
Inspector Notes: The words No Diving on the deck do not meet the minimum height requirement of depth markers: 4 inch lettering. The depth markers at the mushroom/tanning ledge are correct. However, the markers around and in the main pool are incorrect. Code: The words “No Diving” and the universal international symbol for “NO DIVING” shall be permanently visible at the edge of the deck for water five feet in depth or less, placed only on the deck beside the depth markers, and shall conform to that outlined for depth markers in subsections (3)(a) thru (h) above.

Violation #8:
36 – daily recordkeeping: water testing and self inspection performed
511-3-5-.22(12) – (12) a safety self-inspection shall be conducted daily by the trained operator or responsible person and documented on a log sheet.
Points: 5
Corrected during inspection?: No
Repeat: No
Inspector Notes: There is no available documentation onsite to verify a daily safety check is conducted. Code: A safety self-inspection shall be conducted daily by the trained operator or responsible person and documented on a log sheet.

Violation #9:
37 – other violations of the chapter
Points: 1
Corrected during inspection?: No
Repeat: Yes
Inspector Notes: .17(2): The is insufficient calcium hardness in the pool. hardness is required to be at 150 ppm minimum and 1000 ppm maximum. Speak with CPO about adjusting calcium in the pool.

Additional remarks:
Sent text message and spoke to CPO while at the facility to notify of the major violations.